The ABB XT2H 125 MCP In=125 3P F F UL/CSA is a reliable magnetic circuit breaker suitable for various distribution levels. It features front flat terminals, magnetic release, and meets UL and CSA standards for safety and efficiency.
Specifications for XT2H 125 MCP In=125 3p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 14 W
Rated Current (In)
125 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
375â¦1375 A
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. Reliability and Safety
The ABB XT2H 125 MCP In=125 3P F F UL/CSA ensures reliable electrical protection with its magnetic release mechanism, providing a safe and efficient operation.
2. Compliance with Standards
This circuit breaker meets both UL and CSA standards, ensuring it is compliant with the highest safety regulations in the industry.
3. Versatile Application
Ideal for all distribution levels from main low voltage switchboards to subswitchboards, making it a versatile solution for various electrical installations.
4. High Specific Let-Through Current
Features high specific let-through current, allowing it to handle high electrical loads effectively and efficiently.
5. Durable Construction
Built with durable materials, this circuit breaker can withstand heavy usage and maintain its performance over time, ensuring long-term reliability.
600 V
Recommended Screw Driver
Main Circuit M6
Release
MA
Release Type
M
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA (480 V AC) 65 kA (600 V AC) 25 kA (250 V DC) 2 Poles in Series 65 kA (500 V DC) 3 Poles in Series 65 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074890R1