The ABB XT1S 160 TMD 50-500 4P FF is a high-performance, four-pole moulded case circuit breaker with thermomagnetic release, designed for reliable and efficient power distribution in industrial applications. It features a rated current of 160A, a short-circuit breaking capacity of 50kA, and meets IEC standards for electrical durability and safety.
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. High-Performance Design
The ABB XT1S 160 TMD 50-500 4P FF is engineered to provide reliable and efficient power distribution, ensuring minimal downtime and maximum productivity in industrial settings.
2. Thermomagnetic Release (TMD)
Equipped with a thermomagnetic release mechanism, this circuit breaker automatically trips in case of an overload or short circuit, ensuring the safety of personnel and equipment.
3. High Short-Circuit Breaking Capacity
With a short-circuit breaking capacity of 50kA, this circuit breaker can handle high current surges, making it ideal for applications where reliability is crucial.
4. IEC Compliance
Meets IEC standards for electrical durability and safety, ensuring compliance with international safety regulations and best practices.
5. Versatile Application
Suitable for a wide range of industrial applications, including power distribution in transformer, generator, and installation protection systems, the XT1S 160 TMD 50-500 4P FF is a versatile solution for any electrical engineer.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA (230 V AC) 80 kA (240 V AC) 80 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
35...50 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067439R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.