The ABB XT1H 125 TMF 35-500 4P F F UL/CSA is a 4-pole moulded case circuit breaker designed for 35A, 480V applications. It includes a thermomagnetic release and meets UL/CSA standards for safety and reliability.
Specifications for XT1H 125 TMF 35-500 4p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2 W
Rated Current (In)
35 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Operational Voltage
600Y/347 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. Reliable Performance
The XT1H 125 TMF 35-500 4P F F UL/CSA offers reliable performance with a thermomagnetic release, ensuring safe and efficient electrical distribution.
2. UL/CSA Certification
This circuit breaker is certified by UL and CSA, ensuring compliance with North American safety standards for electrical products.
3. Versatile Application
Suitable for both AC and DC applications, this circuit breaker can be used in a variety of electrical systems, including those with 600Y/347V and 500V DC.
4. High Interrupting Rating
With interrupting ratings of 100 kA for 240V AC, 65 kA for 480V AC, and 25 kA for 600Y/347V AC, this circuit breaker provides robust protection against short circuits.
5. Durable Design
Constructed with high-quality materials, this circuit breaker is designed to withstand 8000 cycles of electrical durability and 25000 cycles of mechanical durability, ensuring long-lasting performance in demanding environments.
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
35 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA (480 V AC) 65 kA (600Y / 347 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 4 Poles in Series Kind 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074713R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.