The ABB XT2H 125 TMA 100-500..1000 4P FF UL/CSA circuit breaker is a reliable and safe solution for 600V applications, featuring a TMA trip unit and meeting both UL and CSA standards.
Specifications for XT2H 125 TMA 100-500..1000 4p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 8.1 W
Rated Current (In)
100 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500â¦1000 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. High Reliability and Safety
The XT2H 125 TMA circuit breaker is designed with a TMA trip unit, ensuring reliable and safe operation in 600V applications. Its compliance with UL and CSA standards guarantees high safety standards.
2. Versatile Current Range
This circuit breaker supports a wide range of currents from 100A to 1000A, making it suitable for various industrial and commercial applications.
3. Four-Pole Configuration
The 4P configuration provides enhanced protection and control, ideal for complex electrical systems requiring multiple phases.
4. Compliance with International Standards
The product meets both UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards, ensuring it is compliant with international safety regulations.
5. Durable Design
Constructed with high-quality materials, the XT2H 125 TMA circuit breaker is built to last, offering long-term reliability and performance in demanding electrical environments.
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA (480 V AC) 65 kA (600 V AC) 25 kA (250 V DC) 2 Poles in Series 65 kA (500 V DC) 3 Poles in Series 65 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074814R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.