ABB NF40E-11: A 4-pole contactor relay for switching auxiliary and control circuits, operating on 20-60V AC/DC with 4 NO contacts.
Product ModelNF40E-11
Material Number1SBH137001R1140
Product ID83177
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Versatile Voltage RangeThe ABB NF40E-11 contactor relay operates on a wide voltage range of 20-60V AC/DC, making it suitable for various industrial applications.
2
2. Reliable SwitchingWith 4 normally open (NO) contacts, this relay ensures reliable and efficient switching of auxiliary and control circuits.
3
3. Wide CompatibilityDesigned to work with both AC and DC control circuits, the NF40E-11 is a versatile solution for diverse industrial needs.
4
4. Compact DesignMeasuring 1.77 in W x 3.03 in D x 3.15 in H, the NF40E-11 is a compact yet powerful addition to any control panel.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.27 kg
Number of Auxiliary Contacts NO
4
Number of Auxiliary Contacts NC
0
5. High Contact RatingThe relay has a contact rating of 6 A at 127 VAC, ensuring it can handle the demands of high-current applications with ease.
Standards
IEC/EN 60947-1, IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14-13
(500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)
for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency
(AC-15) 1200 cycles per hour (DC-13) 900 cycles per hour
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)
acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Mechanical Switching Frequency
6000 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation 20 ... 60 V
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms Between Coil De-energization and NO Contact Opening 11 ... 95 ms Between Coil Energization and NC Contact Opening 38 ... 90 ms Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Auxiliary Circuit 11 in·lb Control Circuit 11 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 g Open, Shock Direction: B1 5 g Shock Direction: A 30 g Shock Direction: B2 15 g Shock Direction: C1 25 g Shock Direction: C2 25 g
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz