Manual operation, extended phase distance, and robust construction make the ABB OTM160E2WCM230V a reliable choice for power distribution. Perfect for demanding applications.
Product ModelOTM160E2WCM230V
Material Number1SCA121218R1001
Product ID83137
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Manual OperationEasily switch between power sources with the included handle for manual operation, ensuring seamless transitions and control.
2
2. Extended Phase DistanceThe OTM160E2WCM230V features an extended phase distance, enhancing safety and reducing the risk of electrical shock.
3
3. Robust ConstructionBuilt with high-quality materials, this product offers durability and long-lasting performance in demanding environments.
4
4. Bolt Kit IncludedComes with a bolt kit featuring nuts and washers for all terminals and male connectors for control circuits, ensuring secure connections.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
254 mm 10 in
Product Net Height
170 mm 6.69 in
Product Net Depth / Length
197 mm 7.76 in
Product Net Weight
5.9 kg 13.01 lb
5. Smart DesignDesigned with efficiency in mind, the OTM160E2WCM230V is perfect for applications requiring smart and reliable power distribution solutions.
Conventional Free-air Thermal Current (Ith)
Π= 40 °C 160 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP20
Distance Between Phases
Wide phase distance
Handle Color
Black
Handle Type
Direct mounted handle
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
2P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 2.4 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 160 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 160 A
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Transition Type
Open
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA121218R1001