Compact, current-limiting MCB with delayed thermal tripping and 16A rating. Suitable for residential, commercial, and industrial use.
Product ModelS201M-B16NA
Material Number2CDS271103R0165
Product ID80538
Stock on Request
Last updated: 8/29/2026
Key Features
1
Feature1. Instantaneous Short Circuit Response Type B characteristic offers an instantaneous short circuit response level of 3-5 times the normal rated current, making it suitable for circuits with moderate inrush currents.
2
Feature2. High Short-Circuit Current Capacity Rated for 25 kA short-circuit current, ensuring robust protection against high current surges.
3
Feature3. Compact Design One module width design, ideal for space-constrained applications.
4
Feature4. Flexible Configuration Options Available in various configurations including 1P, 1P+N, 2P, 3P, and 3P+N, catering to diverse circuit requirements.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Standards
IEC/EN 60898-1 CSA 22.2 No. 235 IEC/EN 60947-2 UL 1077
Tripping Characteristic
B
Rated Operational Voltage
acc. to IEC 60898-1 230 V AC acc. to IEC 60898-1 230 V acc. to IEC 60947-2 230 V AC
Operational Voltage
Maximum (Incl. Tolerance) 253 V AC Minimum 12 V AC Minimum 12 V DC
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp)
Feature5. Enhanced Safety Features Real contact position indication (CPI) for easy verification of the contact status, ensuring safety and reliability.
4 kV at 2000 m 5 kV at Sea Level 6.2 kV
Dielectric Test Voltage
50/60 Hz-1 min: 2 kV
Input Voltage Type
AC
Rated Current (In)
16 A
Rated Short-Circuit Capacity
(AC) 10 kA (230 V AC) 10 kA (230 V) 10 kA (400 V) 10 kA