Compact 3-pole mini contactor with one auxiliary contact, suitable for motor control up to 4 kW. Hum-free coils and versatile connections.
Product ModelB6-30-01-F-80
Material NumberGJL1211003R8010
Product ID76974
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe ABB B6-30-01-F-80 mini contactor is designed to save space, making it perfect for applications where space is at a premium. Its shallow depth allows for easy integration into various systems.
2
2. Reliable PerformanceEquipped with hum-free coils, this contactor ensures smooth and reliable operation. It is rated for motor loads up to 4 kW at 400 V and 3 hp at 480 V, providing consistent performance under various conditions.
3
3. Versatile ConnectionsThe B6-30-01-F-80 offers multiple connection types, including screw terminals, soldering pins, and flat pins. This versatility makes it suitable for a wide range of applications and mounting configurations.
4
4. Flexible Mounting OptionsThe contactor can be mounted in any orientation, providing flexibility in installation. This feature is particularly useful in applications where the mounting position may vary.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
52.5 mm
Product Net Height
57.5 mm
Product Net Depth / Length
46.7 mm
Product Net Weight
0.17 kg
Number of Poles
3
Mini Contactor Type
Mini Contactor
5
5. Efficient ControlDesigned for efficient control of single or three-phase loads, the B6-30-01-F-80 mini contactor is ideal for residential, commercial, and industrial applications. It supports both AC and DC control voltages, ensuring compatibility with various systems.
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit 400 Hz Control Circuit 50 Hz Control Circuit 60 Hz Main Circuit 50 Hz Main Circuit 60 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 2.2 kW (400 V) Three Phase 4 kW (500 V) Three Phase 4 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
0
Rated Operational Current AC-15 (Ie)
(24 V) 4 A (120 V) 4 A (500 V) 2 A (220 / 240 V) 4 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Control Circuit Voltage (Uc)
220 ... 240 V AC
Coil Operating Limits
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 5.8 A (200 V AC) Three Phase 4.8 A (220 ... 240 V AC) Three Phase 6.8 A (230 V AC) Single Phase 4.9 A (440 ... 480 V AC) Three Phase 4.8 A (550 ... 600 V AC) Three Phase 1.7 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.25 Hp (200 V AC) Three Phase 1 Hp (220 ... 240 V AC) Three Phase 2 Hp (230 V AC) Single Phase 0.5 Hp (440 ... 480 V AC) Three Phase 3 Hp (550 ... 600 V AC) Three Phase 1 Hp