Compact 3-pole mini reversing contactor with 1 auxiliary contact. Ideal for efficient and safe control in various applications.
Product ModelVBC6A-30-10-P-2.4
Material NumberGJL1213919R5101
Product ID76879
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe VBC6A-30-10-P-2.4 is designed to be compact, making it perfect for space-constrained applications. Its small size allows for easy integration into existing systems without compromising on performance.
2
2. Reliable OperationBuilt with high-quality components, this contactor ensures reliable operation even in demanding environments. Its robust design minimizes the risk of failure, ensuring continuous operation.
3
3. Safety FeaturesEquipped with a mechanical interlock and safety features, the VBC6A-30-10-P-2.4 provides enhanced safety. This ensures that the contactor operates within safe parameters, reducing the risk of electrical hazards.
4
4. Efficient ControlThe contactor features 1 auxiliary contact, allowing for efficient control and monitoring of the circuit. This enhances the overall control and management of the system, making it easier to troubleshoot and maintain.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
96.2 mm
Product Net Height
57.5 mm
Product Net Depth / Length
47.7 mm
Product Net Weight
0.345 kg
Number of Poles
3
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
5
5. Versatile ApplicationsSuitable for a wide range of applications, including industrial automation, marine, and other control systems. Its versatility makes it an ideal choice for various industries requiring efficient and reliable control solutions.
Rated Frequency (f)
Control Circuit DC Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A (220 / 240 V) 55 °C 12 A (380 / 440 V) 40 °C 12 A (380 / 440 V) 55 °C 12 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 2.2 kW (400 V) Three Phase 4 kW (500 V) Three Phase 4 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
1
Rated Operational Current AC-15 (Ie)
(440 V AC) 3 A (24 V) 4 A (120 V) 4 A (240 V) 4 A (500 V) 2 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Control Circuit Voltage (Uc)
17 ... 32 V DC
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Pollution Degree
3
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Remarks
No CA6 or CAF6 mountable
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 5.8 A (200 V AC) Three Phase 4.8 A (220 ... 240 V AC) Three Phase 6.8 A (230 V AC) Single Phase 4.9 A (440 ... 480 V AC) Three Phase 4.8 A (550 ... 600 V AC) Three Phase 1.7 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.25 Hp (200 V AC) Three Phase 1 Hp (220 ... 240 V AC) Three Phase 2 Hp (230 V AC) Single Phase 0.5 Hp (440 ... 480 V AC) Three Phase 3 Hp (550 ... 600 V AC) Three Phase 1 Hp
General Use Rating UL/CSA
(300 V AC) 8 A
Contact Rating UL/CSA
A600
Ambient Air Temperature
Operation -20 ... +55 °C Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000010 - Starter combination
ETIM 6
EC000010 - Combination of contactors
ETIM 7
EC000010 - Combination of contactors
ETIM 8
EC000010 - Combination of contactors
eClass
V11.0 : 27371009
UNSPSC
39121529
Manufacturer ID
GJL1213919R5101
ABB VBC6A-30-10-P-2.4 Mini Reversing Contactor - Compact and Reliable | INDSLT