Product Description: The ABB XT1H 125 MCP In=50 3P F F UL/CSA is a reliable, three-pole molded case circuit breaker designed for UL/CSA standards. It offers magnetic release, front terminals, and a rated current of 50 A, making it suitable for motor protection and efficient electrical distribution.
Specifications for XT1H 125 MCP In=50 3p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH001295R0008
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 3.1 W
Rated Current (In)
50 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
150â¦550 A
Rated Operational Voltage
600Y/347 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. High-Performance Design
The XT1H 125 MCP In=50 3P F F UL/CSA is engineered to provide exceptional performance and reliability, ensuring safe and efficient electrical distribution.
2. Magnetic Release
Equipped with a magnetic release mechanism, this circuit breaker offers quick and reliable operation in case of an overload or short circuit.
3. Front Terminal Connection
Featuring front terminals, the XT1H 125 MCP In=50 3P F F UL/CSA simplifies installation and maintenance, reducing downtime and increasing operational efficiency.
4. UL/CSA Certification
Compliant with UL/CSA standards, this circuit breaker ensures it meets the highest safety and performance requirements, providing peace of mind for users.
5. Motor Protection
Designed specifically for motor protection, the XT1H 125 MCP In=50 3P F F UL/CSA helps safeguard motors from overloads and short circuits, extending their lifespan and improving overall system reliability.
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
MA
Release Type
M
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA (480 V AC) 65 kA (600Y / 347 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 4 Poles in Series Kind 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074728R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?