High-performance, three-pole moulded case circuit breaker with a rated current of 630 A, ensuring reliable electrical protection and efficient operation.
(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 22 kA
Product Highlights
1. Robust Short-Circuit Breaking Capacity
The T6S 800 Ekip M-LRIU In=630 3p F F boasts impressive short-circuit breaking capacities, including 85 kA at 220/230 V AC and 22 kA at 690 V AC, ensuring reliable operation under demanding conditions.
2. Advanced Insulation and Safety Features
Equipped with advanced insulation and safety features, this circuit breaker meets stringent safety standards, including a rated insulation voltage of 1000 V and a rated operational voltage of up to 690 V AC.
3. High Electrical Durability
Designed for long-lasting performance, the T6S 800 Ekip M-LRIU In=630 3p F F can withstand up to 20,000 mechanical cycles and 60 cycles per hour, ensuring consistent operation over time.
4. Versatile Application
Suitable for a wide range of applications, including transformer and generator protection, this circuit breaker is ideal for use in industrial settings where reliability is paramount.
5. Compliance with International Standards
The T6S 800 Ekip M-LRIU In=630 3p F F complies with international standards such as IEC, ensuring compatibility and reliability across various electrical systems.
Rated Uninterrupted Current (Iu)
800 A
Release
Ekip M-LRIU
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060312R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.