ABB T6L 800 TMA 800-8000 3P FF: High-performance moulded case circuit breaker with thermomagnetic release, UL and CSA certified for reliability and safety in industrial applications.
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 80 kA (500 V AC) 65 kA (690 V AC) 30 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 65 kA (750 V DC) 3 Poles in Series 50 kA
Product Highlights
1. High-Performance Design
The ABB T6L 800 TMA 800-8000 3P FF is designed to handle high currents and voltages, ensuring reliable operation in demanding industrial environments.
2. Thermomagnetic Release
Equipped with a thermomagnetic release, this circuit breaker provides both thermal and magnetic trip units for enhanced protection against short circuits and overloads.
3. UL and CSA Certification
Certified by UL and CSA, this product meets stringent safety standards, ensuring it is reliable and safe for use in a variety of industrial applications.
4. Versatile Voltage Range
Compatible with a wide range of voltages, including 690V AC, this circuit breaker is suitable for various industrial settings where different voltage requirements are necessary.
5. Durable Construction
Built with high-quality materials, the ABB T6L 800 TMA 800-8000 3P FF is designed to withstand the rigors of industrial use, with a durable construction that ensures long-lasting performance.
Rated Uninterrupted Current (Iu)
800 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060220R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.