(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 22 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 2 Poles in Series 35 kA (750 V DC) 3 Poles in Series 20 kA
Rated Uninterrupted Current (Iu)
1000 A
Short-Circuit Performance Level
S
Product Highlights
Product Feature
1. High Breaking Capacity The ABB T6S 1000 PR221DS-LS/I boasts a high breaking capacity, with ratings of up to 85 kA at 220 and 230 V AC, ensuring reliable short-circuit protection in various electrical systems.
Product Feature
2. Solid-State Release Equipped with a solid-state release mechanism, this circuit breaker provides fast and accurate tripping, ensuring the safety of electrical equipment and personnel.
Product Feature
3. Electrical Durability Designed to withstand 4000 electrical cycles per hour, this circuit breaker is engineered for long-lasting performance in demanding electrical environments.
Product Feature
4. Compliance with IEC Standards The ABB T6S 1000 PR221DS-LS/I meets IEC standards, ensuring it operates reliably and safely in a wide range of applications, from industrial to commercial settings.
Product Feature
5. Versatile Application With a rated current of 1000A and a three-pole configuration, this circuit breaker is suitable for various applications, including transformer and generator protection, making it a versatile choice for electrical engineers.
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060587R1