The ABB T6S 800 3P FF is a fixed three-pole moulded case circuit breaker with front terminals, designed for reliable and efficient electrical protection. It features a thermal-magnetic trip and meets UL 489 and CSA C22.2 standards, ensuring high performance and safety in various applications.
(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 22 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 2 Poles in Series 35 kA (750 V DC) 3 Poles in Series 20 kA
Rated Uninterrupted Current (Iu)
Product Highlights
1. Reliable Protection
The T6S 800 3P FF provides reliable short-circuit protection with a rated service short-circuit breaking capacity of 10 kA for 1 second.
2. High Performance
Equipped with a thermal-magnetic trip, this circuit breaker ensures efficient operation under various load conditions, providing both thermal and magnetic protection.
3. Compliance with Standards
Meets UL 489 and CSA C22.2 standards, ensuring compliance with North American and international electrical safety regulations.
4. Versatile Application
Suitable for a wide range of applications, including branch circuit protection, transformer, and generator installations, making it a versatile solution for electrical systems.
5. Durable Design
Designed to withstand high electrical durability with up to 20,000 cycles at 120 cycles per hour, ensuring long-lasting performance in demanding environments.
800 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060336R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.