"ABB AFC40-40-00-85 contactor is a 4-pole, 40A device designed for 415VAC and 50/60Hz applications. It is ideal for controlling power circuits in industrial control systems."
Product ModelAFC40-40-00-85
Material Number1SBL341201R8500
Product ID74131
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. High Reliability\"Built with high-quality components, the ABB AFC40-40-00-85 contactor ensures reliable operation in demanding industrial environments.\"
2
2. Versatile Application\"Suitable for a wide range of applications, including 415VAC and 50/60Hz, making it versatile for various industrial control systems.\"
3
3. Efficient Control\"Efficiently control power circuits with the ABB AFC40-40-00-85 contactor, designed to handle 40A and 4-pole configurations.\"
4
4. Easy Installation\"Features screw terminals for easy installation, reducing setup time and increasing productivity in your industrial setup.\"
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
70 mm
Product Net Depth / Length
119.5 mm
Product Net Height
113.5 mm
Product Net Weight
1.18 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
5. Compliance with Standards\"Compliant with IEC and UL standards, ensuring that the ABB AFC40-40-00-85 contactor meets the highest safety and performance standards.\"
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A (690 V) 60 °C 60 A (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A (440 V) 60 °C 40 A (500 V) 60 °C 35 A (690 V) 60 °C 25 A (380 / 400 V) 60 °C 40 A (220 / 230 / 240 V) 60 °C 40 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour (AC-2 / AC-4) 0 cycles per hour
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 380 ... 400 V 60 Hz 400 ... 415 V
Coil Consumption
Average Holding Value 50 / 60 Hz 20 V·A Average Pull-in Value 50 Hz 150 V·A Average Pull-in Value 60 Hz 151 V·A
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 14 ms Between Coil Energization and NO Contact Closing 7 ... 21 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type
Screw Terminals
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb Main Circuit 35 in·lb
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C