High-performance moulded case circuit breaker with thermomagnetic release, front terminals, and a rated current of 80A for reliable electrical distribution.
Product ModelA1N 125 TMF 80-800 3p F F
Material Number
1SDA066729R1
Product ID71641
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable Thermomagnetic ReleaseThe ABB A1N 125 TMF 80-800 3p F F features a thermomagnetic release mechanism, ensuring safe and efficient operation under various load conditions.
2
2. Front Terminal DesignEquipped with front terminals, this circuit breaker offers easy and convenient installation, reducing setup time and improving overall efficiency.
3
3. High Rated CurrentWith a rated current of 80A, this three-pole circuit breaker is capable of handling significant electrical loads, making it suitable for demanding industrial applications.
4
4. Compliance with International StandardsDesigned to meet IEC standards, the ABB A1N 125 TMF 80-800 3p F F ensures compatibility and reliability in diverse global environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
1SDL000183R0001 9AKK108467A6707
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
0.798 kg
Product Main Type
SACE FORMULA
5
5. Durable ConstructionBuilt to withstand 1500 operational cycles, this moulded case circuit breaker offers long-lasting performance and durability, reducing the need for frequent replacements.
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Power Loss
at Rated Operating Conditions per Pole 9 W
Rated Current (In)
Main Circuit 80 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA (380 V AC) 18 kA (415 V AC) 7.5 kA (440 V AC) 6.25 kA (480 V AC) 4.5 kA (500 V AC) 2.5 kA (250 V DC) 2 Poles in Series 5 kA