Short Description: Compact 3-pole miniature contactor with low coil consumption, suitable for direct PLC control, and ideal for residential, commercial, and industrial applications.
Product ModelBC7-30-01-2.4-54
Material NumberGJL1313001R5014
Product ID71271
Stock on Request
Last updated: 8/29/2026
Key Features
1
Feature1. Reliable Operation The ABB BC7-30-01-2.4-54 contactor ensures reliable operation with a high number of operating cycles (up to 10 million) and a wide operating temperature range (-25 to 55°C).
2
Feature2. Low Coil Consumption Designed for low coil consumption, this contactor is energy-efficient and can be directly controlled by a PLC, making it suitable for various control applications.
3
Feature3. Noiseless Operation Featuring a hum-free coil, the BC7-30-01-2.4-54 minimizes noise, ensuring a quiet and efficient operation in any environment.
4
Feature4. Compact Design With dimensions of 2.07 in W x 1.84 in D x 2.26 in H, this contactor is compact and ideal for applications where space is at a premium.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
52.5 mm
Product Net Height
57.5 mm
Product Net Depth / Length
46.7 mm
Product Net Weight
0.175 kg
Number of Poles
3P
Mini Contactor Type
Interface Mini Contactor
5
Feature5. Versatile Mounting Options The contactor offers integrated rail or wall mounting options, providing flexibility in installation and making it easy to integrate into various control systems.
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC Main Circuit 50 Hz Main Circuit 60 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW (400 V) Three Phase 5.5 kW (500 V) Three Phase 5.5 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
0
Rated Operational Current AC-15 (Ie)
(24 V) 4 A (120 V) 4 A (500 V) 2 A (220 / 240 V) 4 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Control Circuit Voltage (Uc)
36 ... 65 V DC
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply Uc Min. ... Uc Max. (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Auxiliary Circuit 0.8 ... 1.1 N·m Control Circuit 0.8 ... 1.1 N·m Main Circuit 0.8 ... 1.1 N·m
Recommended Screw Driver
M3 Pozidriv 1
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1
Remarks
No CA6 or CAF6 mountable
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A (200 V AC) Three Phase 7.8 A (220 ... 240 V AC) Three Phase 9.6 A (230 V AC) Single Phase 10 A (440 ... 480 V AC) Three Phase 7.6 A (550 ... 600 V AC) Three Phase 6.1 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp (200 V AC) Three Phase 2 Hp (220 ... 240 V AC) Three Phase 3 Hp (230 V AC) Single Phase 1.5 Hp (440 ... 480 V AC) Three Phase 5 Hp (550 ... 600 V AC) Three Phase 5 Hp
General Use Rating UL/CSA
(600 V AC) 16 A
Contact Rating UL/CSA
A600
Connecting Capacity Main Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 7 in·lb Control Circuit 7 in·lb Main Circuit 7 in·lb