Compact 3-pole mini reversing contactor with 1 auxiliary contact, suitable for controlling three-phase motor loads up to 4 kW (AC-3).
Product ModelVB6-30-10-F-01
Material NumberGJL1211903R0101
Product ID71270
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe VB6-30-10-F-01 is designed to be compact, making it ideal for applications where space is at a premium. Its dimensions allow for easy installation in various settings.
2
2. ReliabilityThis contactor features a built-in mechanical interlock and hum-free coils, ensuring high reliability and minimizing the risk of electrical faults. The coils are also mutually interlocked electrically to prevent phase-to-phase short circuits.
3
3. Efficient OperationWith a low coil consumption of 3.5 VA at pull-in and holding, the VB6-30-10-F-01 operates efficiently, reducing energy costs and minimizing heat generation.
4
4. Versatile ApplicationsSuitable for residential, commercial, and industrial applications, this contactor can control three-phase motor loads up to 4 kW (AC-3). It is particularly useful in HVAC systems, pumps, and other motor-driven equipment.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
96.2 mm
Product Net Height
57.5 mm
Product Net Depth / Length
46.7 mm
Product Net Weight
0.345 kg
Number of Poles
3P
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
5
5. Easy InstallationThe contactor offers integrated possibilities for rail or wall mounting, making installation quick and hassle-free. The screw terminals and cable clamp connections provide a secure and reliable connection method.
Rated Frequency (f)
Control Circuit 400 Hz Control Circuit 50 Hz Control Circuit 60 Hz Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 2.2 kW (400 V) Three Phase 4 kW (500 V) Three Phase 4 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
1
Rated Operational Current AC-15 (Ie)
(440 V AC) 3 A (24 V) 4 A (120 V) 4 A (240 V) 4 A (500 V) 2 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Control Circuit Voltage (Uc)
24 V AC
Coil Operating Limits
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C) (acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Pollution Degree
3
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 5.8 A (200 V AC) Three Phase 4.8 A (220 ... 240 V AC) Three Phase 6.8 A (230 V AC) Single Phase 4.9 A (440 ... 480 V AC) Three Phase 4.8 A (550 ... 600 V AC) Three Phase 1.7 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.25 Hp (200 V AC) Three Phase 1 Hp (220 ... 240 V AC) Three Phase 2 Hp (230 V AC) Single Phase 0.5 Hp (440 ... 480 V AC) Three Phase 3 Hp (550 ... 600 V AC) Three Phase 1 Hp
General Use Rating UL/CSA
(300 V AC) 12 A
Contact Rating UL/CSA
A600
Ambient Air Temperature
Operation -20 ... +55 °C Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000010 - Starter combination
ETIM 6
EC000010 - Combination of contactors
ETIM 7
EC000010 - Combination of contactors
ETIM 8
EC000010 - Combination of contactors
eClass
V11.0 : 27371009
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4761 >> Magnet contactor, AC-switching
Manufacturer ID
GJL1211903R0101