The ABB XT1C160 TMD 32/450 4P FFC is a fixed four-pole moulded case circuit breaker with front terminals and thermomagnetic release. It features a rated current of 32 A and is designed to handle high short-circuit currents, making it ideal for transformer, generator, and installation protection applications.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
C
Standards
IEC60947-2 GB/T 14028.2
Product Highlights
1. High Breaking Capacity
The XT1C160 TMD 32/450 4P FFC boasts a breaking capacity of 25 kA, ensuring reliable operation even under extreme short-circuit conditions.
2. Thermomagnetic Release
Equipped with a thermomagnetic release (TMD), this circuit breaker provides a reliable and efficient way to interrupt electrical currents, ensuring safe and uninterrupted operation.
3. Four-Pole Configuration
Designed as a four-pole circuit breaker, it can handle multiple phases, making it versatile for various electrical systems and applications.
4. Front Terminal Connection
The front terminal connection makes it easy to install and maintain, reducing the complexity of electrical connections.
5. Compliance with IEC Standards
The XT1C160 TMD 32/450 4P FFC meets IEC standards, ensuring compliance with international safety and performance regulations, providing peace of mind for users.
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100062R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.