Compact 3-pole mini contactor for reliable control of loads up to 5.5 kW. Silent coil, switch position indication, and rail mounting.
Product ModelB7-30-10-P-80
Material NumberGJL1311009R8100
Product ID70817
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe ABB B7-30-10-P-80 is a space-saving solution, perfect for applications where space is at a premium.
2
2. Reliable OperationDesigned for high reliability, this mini contactor ensures consistent performance in residential, commercial, and industrial settings.
3
3. Silent Coil OperationThe silent coil feature minimizes noise, making it suitable for applications where noise reduction is important.
4
4. Switch Position IndicationThe switch position indication feature provides clear visibility of the contactor's status, enhancing operational efficiency.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
47.5 mm
Product Net Height
45.2 mm
Product Net Depth / Length
47.7 mm
Product Net Weight
0.17 kg
Number of Poles
3
Mini Contactor Type
Mini Contactor
5. Integrated Rail MountingThe integrated rail mounting option allows for easy installation and flexibility in mounting configurations, making it versatile for various applications.
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit 400 Hz Control Circuit 50 Hz Control Circuit 60 Hz Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A (220 / 240 V) 55 °C 12 A (380 / 440 V) 40 °C 12 A (380 / 440 V) 55 °C 12 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW (400 V) Three Phase 5.5 kW (500 V) Three Phase 5.5 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
1
Rated Operational Current AC-15 (Ie)
(24 V) 4 A (120 V) 4 A (500 V) 2 A (220 / 240 V) 4 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Control Circuit Voltage (Uc)
220 ... 240 V AC
Coil Operating Limits
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A (200 V AC) Three Phase 7.8 A (220 ... 240 V AC) Three Phase 9.6 A (230 V AC) Single Phase 10 A (440 ... 480 V AC) Three Phase 7.6 A (550 ... 600 V AC) Three Phase 6.1 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp (200 V AC) Three Phase 2 Hp (220 ... 240 V AC) Three Phase 3 Hp (230 V AC) Single Phase 1.5 Hp (440 ... 480 V AC) Three Phase 5 Hp (550 ... 600 V AC) Three Phase 5 Hp