High-performance, three-pole moulded case circuit breaker with thermomagnetic release (TMD) for reliable power distribution, meeting IEC standards.
Product ModelXT3S 250 TMD 63-630 3p F F
Material Number1SDA068215R1
Product ID70569
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable Power DistributionThe ABB XT3S 250 TMD 63-630 3p F F ensures reliable power distribution with its robust design and high-quality components, making it ideal for various industrial applications.
2
2. Thermomagnetic Release (TMD)Equipped with a thermomagnetic release, this circuit breaker provides efficient and safe operation under various load conditions, ensuring minimal downtime and maximum safety.
3
3. Compliance with IEC StandardsMeets IEC standards for electrical durability and performance, ensuring that the circuit breaker operates within specified parameters, enhancing overall system reliability and safety.
4
4. Versatile ApplicationSuitable for a wide range of applications, including power distribution in industrial settings, it can handle currents up to 250 A and short-circuit currents up to 630 A.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.7 kg
Circuit Breaker Type to be Associated
Power Distribution
5
5. Durable ConstructionBuilt with durable materials, this circuit breaker has a long operational life and can withstand frequent operations, making it a reliable choice for long-term use in demanding environments.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0409
Connecting Capacity Main Circuit
Busbar 85..192 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.3 W
Rated Current (In)
63 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
630 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 27 kA (415 V AC) 36 kA (440 V AC) 20 kA (500 V AC) 15 kA (525 V AC) 10 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 27 kA (500 V DC) 3 Poles in Series 37.5 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M8
Release
TMD
Release Type
TM
Setting Range
44.1...63 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT3
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA068215R1
ABB XT3S 250 TMD 63-630 3p F F - High-Performance Circuit Breaker | INDPRT