The ABB XT1N160 TMD160/1600 FFC 4P+RC Inst is a high-performance, four-pole circuit breaker with a thermomagnetic release, designed for reliable and efficient power distribution. It is fully rated for neutral, ensuring maximum safety and durability.
Specifications for XT1N160 TMD160/1600 FFC 4P+RC Inst
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
2.7 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Product Highlights
1. High-Performance Design
The ABB XT1N160 TMD160/1600 FFC 4P+RC Inst is engineered to provide reliable and efficient power distribution, making it ideal for demanding applications.
2. Thermomagnetic Release
Equipped with a thermomagnetic release, this circuit breaker ensures safe and reliable operation under various conditions, including high short-circuit currents.
3. Fully Rated for Neutral
Designed to handle full-rated currents in neutral, this circuit breaker provides maximum safety and durability, reducing the risk of electrical failures.
4. Four-Pole Configuration
The four-pole configuration allows for flexible and efficient power distribution, making it suitable for a wide range of applications, from industrial to commercial settings.
5. Compliance with IEC Standards
The XT1N160 TMD160/1600 FFC 4P+RC Inst complies with IEC standards, ensuring that it meets the highest safety and performance requirements, providing peace of mind for users.
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100498R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.