Short Description: Compact 3-pole mini contactor with 1 auxiliary contact, suitable for direct PLC control, and ideal for residential, commercial, and industrial applications.
Product ModelBC7-30-01-1.4-81
Material NumberGJL1313001R8011
Product ID69649
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe BC7-30-01-1.4-81 mini contactor is designed to be compact, making it ideal for applications where space is at a premium. Its small size allows for easy integration into various systems.
2
2. Reliable PerformanceThis contactor is built for reliability, ensuring consistent performance in a wide range of applications. It is suitable for controlling single or three-phase loads up to 5.5 kW (AC-3) and 20 A / 690 V (AC-1).
3
3. Low Coil ConsumptionThe device features a low coil consumption, which makes it energy-efficient and suitable for direct control by PLC outputs. This reduces power consumption and extends the lifespan of the contactor.
4
4. Noiseless and Hum-Free CoilThe contactor has a noiseless and hum-free coil, providing a quiet operation that is essential in many industrial and commercial settings. This feature ensures that the device does not disrupt the environment or interfere with other equipment.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
52.5 mm
Product Net Height
57.5 mm
Product Net Depth / Length
46.7 mm
Product Net Weight
0.175 kg
Number of Poles
3
Mini Contactor Type
Interface Mini Contactor
5
5. Versatile Mounting OptionsThe BC7-30-01-1.4-81 contactor offers integrated possibilities for rail or wall mounting, providing flexibility in installation. This makes it easy to integrate into various system configurations and environments.
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW (400 V) Three Phase 5.5 kW (500 V) Three Phase 5.5 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
0
Rated Operational Current AC-15 (Ie)
(24 V) 4 A (120 V) 4 A (500 V) 2 A (220 / 240 V) 4 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Control Circuit Voltage (Uc)
24 V DC
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Auxiliary Circuit 0.8 ... 1.1 N·m Control Circuit 0.8 ... 1.1 N·m Main Circuit 0.8 ... 1.1 N·m
Recommended Screw Driver
M3 Pozidriv 1
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Remarks
No CA6 or CAF6 mountable
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A (200 V AC) Three Phase 7.8 A (220 ... 240 V AC) Three Phase 9.6 A (230 V AC) Single Phase 10 A (440 ... 480 V AC) Three Phase 7.6 A (550 ... 600 V AC) Three Phase 6.1 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp (200 V AC) Three Phase 2 Hp (220 ... 240 V AC) Three Phase 3 Hp (230 V AC) Single Phase 1.5 Hp (440 ... 480 V AC) Three Phase 5 Hp (550 ... 600 V AC) Three Phase 5 Hp
General Use Rating UL/CSA
(600 V AC) 16 A
Contact Rating UL/CSA
A600
Connecting Capacity Main Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 7 in·lb Control Circuit 7 in·lb Main Circuit 7 in·lb