Short Description: ABB F204 A-80/0.3-L 4P Type AC 300 mA Residual Current Circuit Breaker for standard instantaneous and selective protection against fault currents to earth.
Product ModelF204 A-80/0.3-L
Material Number2CSF204123R3800
Product ID69613
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Protection Against Fault CurrentsThe ABB F204 A-80/0.3-L provides comprehensive protection against fault currents to earth, ensuring the safety of people and installations.
2
2. Selective and Instantaneous ProtectionThis product offers both selective and instantaneous protection, making it suitable for a wide range of applications, from residential to industrial settings.
3
3. 4-Pole ConfigurationThe 4-pole configuration allows for multi-wired connections, enhancing flexibility and reliability in electrical installations.
4
4. High Sensitivity and AccuracyWith a rated residual current of 300 mA, this circuit breaker ensures high sensitivity and accuracy in detecting earth faults, providing reliable protection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Standards
IEC/EN 61008
Type of Residual Current
Type A
Rated Voltage (Ur)
230/400 V
Rated Operational Voltage
230 / 400 V AC
Rated Insulation Voltage (Ui)
500 V
Test Voltage (Ut)
195-440 V
5
5. Compliance with International StandardsThe ABB F204 A-80/0.3-L conforms to IEC/EN 61008 and UL 1053 standards, ensuring compliance with international safety regulations.
Rated Impulse Withstand Voltage (Uimp)
4 kV
Input Voltage Type
AC
Rated Current (In)
80 A
Rated Residual Current
300 mA
Rated Conditional Short-Circuit Current (Inc)
10 kA
Leakage Current Type
A
Frequency (f)
50/60 Hz
Rated Frequency (f)
50 ⦠60 Hz
Power Loss
at Rated Operating Conditions per Pole 5.3 W
Power Supply Connection
Arbitrary
Electrical Endurance
10000 cycle
Number of Poles
4
Number of Modular Spacings per DIN Rail
4
Operating Characteristic
Instantaneous
Position of Neutral Terminals
Left
Tightening Torque
2.8 N·m
Accessory Type