Compact, mechanically interlocked 3-pole contactor for 220-240V applications. Ideal for residential, commercial, and industrial use.
Product ModelVB6A-30-01-80
Material NumberGJL1211911R8010
Product ID69418
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe ABB VB6A-30-01-80 is designed to be compact, making it perfect for applications where space is limited. Its small size allows for easy integration into various electrical systems without taking up too much room.
2
2. Mechanical InterlockEquipped with a built-in mechanical interlock, this contactor ensures safety by preventing accidental phase-to-phase short circuits. This feature is crucial for maintaining the integrity of electrical circuits.
3
3. ReliabilityDesigned for reliability, the VB6A-30-01-80 is engineered to handle high operational cycles. It can withstand up to 10 million cycles, ensuring consistent performance over time.
4
4. Versatile ApplicationsSuitable for a wide range of applications including residential buildings, commercial spaces, and industrial settings. It can control three-phase motor loads up to 4 kW, making it versatile for various electrical needs.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
96.2 mm
Product Net Height
57.5 mm
Product Net Depth / Length
46.7 mm
Product Net Weight
0.355 kg
Number of Poles
3
Rated Operational Voltage
Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC
5
5. Efficient Coil ConsumptionThe contactor features a low coil consumption design, which reduces energy waste. It operates at 3.5 VA at both pull-in and holding states, making it an energy-efficient solution for your electrical needs.
Rated Frequency (f)
Control Circuit 400 Hz Control Circuit 50 Hz Control Circuit 60 Hz Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 2.2 kW (400 V) Three Phase 4 kW (500 V) Three Phase 4 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
0
Rated Operational Current AC-15 (Ie)
(440 V AC) 3 A (24 V) 4 A (120 V) 4 A (240 V) 4 A (500 V) 2 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Control Circuit Voltage (Uc)
220 ... 240 V AC
Coil Operating Limits
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C) (acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20
Pollution Degree
3
Mechanical Durability
10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour
Control Circuit 0.8 ... 1.1 N·m Main Circuit 0.8 ... 1.1 N·m
Recommended Screw Driver
M3 Pozidriv 1
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 5.8 A (200 V AC) Three Phase 4.8 A (220 ... 240 V AC) Three Phase 6.8 A (230 V AC) Single Phase 4.9 A (440 ... 480 V AC) Three Phase 4.8 A (550 ... 600 V AC) Three Phase 1.7 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.25 Hp (200 V AC) Three Phase 1 Hp (220 ... 240 V AC) Three Phase 2 Hp (230 V AC) Single Phase 0.5 Hp (440 ... 480 V AC) Three Phase 3 Hp (550 ... 600 V AC) Three Phase 1 Hp
General Use Rating UL/CSA
(300 V AC) 12 A
Contact Rating UL/CSA
A600
Connecting Capacity Main Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 7 in·lb Control Circuit 7 in·lb Main Circuit 7 in·lb