Compact 4-Pole Mini Contactor for Reliable Load Control. Ideal for residential, commercial, and industrial use with noiseless coil and switch position indication.
Product ModelBC7-40-00-P-01
Material NumberGJL1313209R0001
Product ID69359
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Compact DesignThe ABB BC7-40-00-P-01 is designed to be compact, making it perfect for applications where space is at a premium. Its dimensions ensure it fits seamlessly into various installations.
2
2. ReliabilityThis contactor is built for reliability, ensuring consistent performance in demanding environments. Its noiseless and hum-free coil operation minimizes disturbances, providing a smooth control experience.
3
3. Versatile ApplicationsSuitable for residential buildings, commercial spaces, and industrial applications, the BC7-40-00-P-01 can control single or three-phase loads up to 5.5 kW (AC-3) and 20 A / 690 V (AC-1).
4
4. Easy InstallationWith integrated possibilities for rail or wall mounting, the contactor is easy to install in various settings. The screw terminals provide a secure connection, ensuring reliable operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
47.5 mm
Product Net Height
45.2 mm
Product Net Depth / Length
47.7 mm
Product Net Weight
0.17 kg
Number of Poles
4
Mini Contactor Type
Mini Contactor
5
5. Switch Position IndicationThe contactor features a switch position indication, allowing users to easily monitor its status. This feature enhances safety and operational efficiency by providing clear visual feedback.
Rated Operational Voltage
Main Circuit 690 V AC Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
4
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A (220 / 240 V) 55 °C 12 A (380 / 440 V) 40 °C 12 A (380 / 440 V) 55 °C 12 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW (400 V) Three Phase 5.5 kW (500 V) Three Phase 5.5 kW (690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Control Circuit Voltage (Uc)
24 V DC
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C)
Degree of Protection
Control Circuit Terminals IP20 Main Circuit Terminals IP20
Mechanical Durability
10000000 cycle
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-3) 600 cycles per hour
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Standards
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A (200 V AC) Three Phase 7.8 A (220 ... 240 V AC) Three Phase 9.6 A (230 V AC) Single Phase 10 A (440 ... 480 V AC) Three Phase 7.6 A (550 ... 600 V AC) Three Phase 6.1 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp (200 V AC) Three Phase 2 Hp (220 ... 240 V AC) Three Phase 3 Hp (230 V AC) Single Phase 1.5 Hp (440 ... 480 V AC) Three Phase 5 Hp (550 ... 600 V AC) Three Phase 5 Hp