24 VDC (-25 +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Current consumption, field supply (module with no external load)
20mA
Isolation
500 V system/field
Indicators
LED (1, 8, 9, 15) green: Signal Status DI 1, Undervoltage, Signal Status DI 2, Parameterization Status; LED (3, 5, 11, 13) yellow: Setpoint, Dithering Channel A, B; LED (4, 6) red/green: Status Channel A, B; LED (7, 16) red: Initialization, Error
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Connection technology: inputs / outputs
16 x Push-in CAGE CLAMP®
Connection type 1
Inputs/Outputs
Solid conductor
0.08 1.5 m㎡/ 28 16 AWG
Fine-stranded conductor
0.25 1.5 m㎡/ 22 16 AWG
Strip length
8 9 mm / 0.31 0.35 inches
Connection requirement (permissible cable length)
30m
Connection requirement (permissible cable type)
Outputs
Note (conductor cross-section)
Coil connections A+/A-/B+/B-: 1.5 mm2/16 AWG; For use according to UL 508: 16 AWG for all connections
Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
69 mm / 2.717 inches
Depth from upper-edge of DIN-rail
61.8 mm / 2.433 inches
Mounting type
DIN-35 rail
Color
light gray
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.848MJ
Weight
54.4g
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-40 … 85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 2000 m / 0 6562 ft
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)
95%
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-4, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%