WAGO 2216-7111 is a 1-conductor power distribution disconnect terminal block with a push-button and Push-in CAGE CLAMP technology, suitable for DIN rail mounting.
Product Model2216-7111
Product ID49109
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureEasy Connection
2
FeatureVersatile Clamping
3
FeatureCompact Design
4
FeatureReliable Technology
5
FeatureSafety and Compliance
6
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Clamping units
1
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
12 mm / 0.472 inches
Height
69.4 mm / 2.732 inches
FeatureEasy Connection
7
FeatureVersatile Clamping
8
FeatureCompact Design
9
FeatureReliable Technology
10
FeatureSafety and Compliance
Depth from upper-edge of DIN-rail
38.1 mm / 1.5 inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Fine-stranded conductor; with ferrule; push-in termination
6 16 m㎡/ 10 6 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.AWG specifications were converted according to IEC.
Strip length
18 20 mm / 0.71 0.79 inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications <br/>Rolling stock <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications <br/>Rolling stock equipment <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category 1, Class A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment