2 bits (1 bit current monitoring, 1 bit fuse fault)
Supply voltage (system)
5 VDC; Via data contacts
Current consumption (5 V system supply)
5mA
Supply voltage (field)
24 VDC (-25 +30 %); Via power jumper contacts (power supply via CAGE CLAMP®connection; transmission via spring contact); Derating must be observed!
Rated surge voltage
1 kV
Indicators
LED (A) red: defective fuse error; LED (B) green: power supply status
Number of outgoing power jumper contacts
2
Current carrying capacity (power jumper contacts)
6.3A
Derating
Derating (supply voltage):Ambient temperatures under laboratory conditions: (?25 +30°%);for ?40 +55掳°C: 24掳V (?25 +20°%);for +55 +70°°C: 24掳V (?25 +10°%);Lower limit in all temperature ranges: ?27.5°% (including 15°% residual ripple)
Connection technology: field supply
6 x CAGE CLAMP®
Connection type 1
Field supply
Solid conductor
0.25 2.5 m㎡/ 24 14 AWG
Fine-stranded conductor
0.25 2.5 m㎡/ 24 14 AWG
Strip length
8 9 mm / 0.31 0.35 inches
Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches
Mounting type
DIN-35 rail
Color
dark gray
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.995MJ
Weight
46.8g
Conformity marking
CE
Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … 85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 2000 m; with temperature derating: 2000 5000 m (0.5 K/100 m); 5000 m (max.)
Mounting position
Horizontal left, horizontal up, vertical top and vertical bottom
Relative humidity (without condensation)
95%
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference
per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%