24 VDC (-25 +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Current consumption, field supply (module with no external load)
20mA
Isolation
500 V system/field
Indicators
LED (1, 8, 9, 15) green: Signal Status DI 1, Undervoltage, Signal Status DI 2, Parameterization Status; LED (3, 5, 11, 13) yellow: Setpoint, Dithering Channel A, B; LED (4, 6) red/green: Status Channel A, B; LED (7, 16) red: Initialization, Error
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Connection technology: inputs / outputs
16 x Push-in CAGE CLAMP®
Connection type 1
Input/output
Connectable conductor materials
Copper
Solid conductor
0.08 1.5 mm2 / 28 16 AWG
Fine-stranded conductor
0.25 1.5 mm2 / 22 16 AWG
Strip length
8 9 mm / 0.31 0.35 inches
Connection requirement (permissible cable length)
30m
Connection requirement (permissible cable type)
Outputs
Note (conductor cross-section)
Coil connections A+/A-/B+/B-: 1.5 mm2/16 AWG; For use according to UL 508: 16 AWG for all connections
Temperature range of connection cable
The permissible temperature range of the connecting cable must be dimensioned depending on the mounting position and current intensity because the temperature of the terminal connection can be up to 25°C (at 10°A) above the maximum expected ambient temperature.
Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
69 mm / 2.717 inches
Depth from upper-edge of DIN-rail
61.8 mm / 2.433 inches
Mounting type
DIN-35 rail
Pluggable connector
fixed
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.848MJ
Weight
53.6g
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 2000 m / 0 6562 ft
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)
95%
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-4, marine applications
Exposure to pollutants
per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%