Programmable logic controller with 24VDC, multiple communication interfaces, and extended temperature range.
Product Model750-8208/025-001
Product ID44634
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureAdvanced programmable logic controller with Codesys support
2
FeatureMultiple communication interfaces including Ethernet, RS-232/-485, CAN, CANopen, and PROFIBUS-Master
3
FeatureSupports Modbus (TCP, UDP) and Modbus RTU protocols
4
FeatureExtended temperature range for robust operation
5
FeatureDIN Rail form factor for easy installation
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Communications
PROFIBUS DP master
ETHERNET protocols
DHCP
Telecontrol protocols
IEC 60870
Visualization
Web-Visu
Operating system
Real-time Linux (with PREEMPT_RT patch)
CPU
Cortex A8; 600 MHz
Programming languages per IEC 61131-3
Instruction List (IL)
Programming environment
WAGO-I/O-PROV2.3 (based on CODESYS V2.3)
Configuration options
WAGO-I/O-CHECK
Transmission rate
ETHERNET: 10/100 mbit/s
Transmission medium (communication/fieldbus)
ETHERNET: Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
Main memory (RAM)
256MB
Internal memory (flash)
256MB
Non-volatile hardware memory
128Kbytes
Program memory
16 mB
Data memory
64 mB
Non-volatile software memory
128Kbytes
Type of memory card
SD card
Memory card slot
Push-push mechanism; Cover lid (sealable)
Number of modules per node (max.)
250
Number of modules without a bus extension (max.)
64
Input and output process image (internal) max.
1000 Words/1000 Words
Input and output process image (Modbus®) max.
CODESYS V2: 1000 Words/1000 Words
Input and output process image (PROFIBUS) max.
5000 bytes/5000 bytes
Input and output process image (CAN) max.
2000 Words/2000 Words
Indicators
LED (SYS, RUN, I/O, CAN, BF, DIA, U1 U4) red/green/orange: Status system, program, internal data bus, CANopen, PROFIBUS, PROFIBUS diagnostics, status programmable by user (can be used via CODESYS library); LED (A, B) green: System power supply status, field supply
Supply voltage (system)
24 VDC (-25 +30 %); Via pluggable connector (CAGE CLAMP®connection)
Input current (typ.) at nominal load (24 V)
670mA
Total current (system supply)
1,700mA
Supply voltage (field)
24 VDC (-25 +30 %); Via power jumper contacts
Current carrying capacity (power jumper contacts)
10A
Number of outgoing power jumper contacts
3
Isolation
500 V system/field
Connection technology: communication/fieldbus
PROFIBUS: 1 x D-sub 9 socket; CANopen: 1 x D-sub 9 plug; modbus (TCP, UDP): 2 x RJ-45; modbus RTU: 1 x D-sub 9 socket; RS-232 serial interface: 1 x D-sub 9 socket; RS-4852 interface: 1 x D-sub 9 socket;?Telecontrol protocol IEC 60870-5-101/-103: 1 x D-sub 9 socket;?Telecontrol protocol IEC 60870-5-104:?1 x RJ-45;?Telecontrol protocol IEC 61850:?1 x RJ-45;?Telecontrol protocol DNP3:?1 x RJ-45 or D-sub 9 socket
Connection technology: system supply
2 x CAGE CLAMP®
Connection technology: field supply
6 x CAGE CLAMP®
Connection type 1
System/field supply
Solid conductor
0.08 … 2.5 mm2 / 28 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm2 / 28 14 AWG
Strip length
8 9 mm / 0.31 0.35 inches
Connection technology: device configuration
1 x Male connector; 4-pole
Width
112 mm / 4.409 inches
Height
100 mm / 3.937 inches
Depth
71.9 mm / 2.831 inches
Depth from upper-edge of DIN-rail
64.7 mm / 2.547 inches
Weight
263.7g
Housing material
Polycarbonate; polyamide 6.6
Conformity marking
CE
Ambient temperature (operation)
-20 … +60 °C
Ambient temperature (storage)
-40 … 85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
without temperature derating: 0 2000 m; with temperature derating: 2000 5000 m (0.5 K/100 m); 5000 m (max.)
Relative humidity (without condensation)
95%
Relative humidity (with condensation)
Short-term condensation per Class 3K6/IEC EN 60721-3-3 and E-DIN 40046-721-3, accounting for a temperature range of ?20 ?to +60 °C (except for wind-driven precipitation, water and ice formation)
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Mounting type
DIN-35 rail
Vibration resistance
per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-3, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Fire load
2.881MJ
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%