Fixed for current signals, input: 0(4) … 20 mA, output: 0(4) … 20 mA.
Product Model857-411
Product ID44298
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureFixed for current signals
2
Input0(4) … 20 mA
3
Output0(4) … 20 mA
4
Supply voltage24 VDC
5
Feature6 mm module width
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Safety information
Input and output must be safely isolated from any hazardous live parts!
Note
The 3 (Us+), 7 (Us+), 4 (GND 3) and 8 (GND 3) connections are internally commoned.Current carrying capacity between 3/4 and 7/8 connections: 1 A (max.)
Rated voltage
300V
Protection type
IP20
Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.08 … 2.5 mm2 / 28 14 AWG
Fine-stranded conductor
0.34 2.5 m㎡/ 22 14 AWG
Strip length
9 10 mm / 0.35 0.39 inches
Width
6 mm / 0.236 inches
Height
94 mm / 3.701 inches
Depth from upper-edge of DIN-rail
97.8 mm / 3.85 inches
Mounting type
DIN-35 rail
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.543MJ
Weight
36.1g
Ambient temperature (operation)
-25 … +70 °C
Ambient temperature (storage)
-40 … 85 °C
Processing temperature
-25 … +50 °C
Temperature range of connection cable
≤ (Tambient+ 25 K)
Relative humidity
5 95 % (no condensation permissible)
Operating altitude (max.)
2000m
Conformity marking
CE
EMC immunity to interference
EN 61000-6-2
EMC emission of interference
EN 61000-6-4
Standards/specifications
EN 61010-1
Product Group
6 (INTERFACE ELECTRONIC)
eCl@ss 10.0
27-21-01-20
eCl@ss 9.0
27-21-01-20
ETIM 9.0
EC002653
ETIM 8.0
EC002653
ECCN
NO US CLASSIFICATION
PU (SPU)
1 pcs
Packaging type
bag
Country of origin
DE
GTIN
4045454471224
Customs tariff number
8543704500
CAS-No.
1303-86-2
REACH Candidate List Substance
Diboron trioxide
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
6(c)
SCIP notification number (Austria)
e1a379a9-9a12-43c5-ba97-78cd431a5012
SCIP notification number (Belgium)
a3504f54-5762-4675-86e4-06b3a5cee394
SCIP notification number (Bulgaria)
329d10ce-3573-4f6f-967f-f227f641d686
SCIP notification number (Czech Republic)
ccbda9d3-1048-44d4-b2ae-66419bd577c0
SCIP notification number (Denmark)
2e5f76a3-2103-4880-b174-4de45b1ae8e4
SCIP notification number (Finland)
32b6734a-1a59-449b-93fd-5bd651f6e1b1
SCIP notification number (France)
162cb9fc-1c93-4dec-8237-9d60232fce19
SCIP notification number (Germany)
d027a0a8-794c-4140-8453-02e9ad261de5
SCIP notification number (Hungary)
e3e4fe82-951e-453c-8d9a-1e47f1e3b45c
SCIP notification number (Italy)
69b859ca-7aa5-448e-9028-7034acee6015
SCIP notification number (Netherlands)
4cbf5e0d-e6fb-4d36-8761-6888a0c18909
SCIP notification number (Poland)
64e2711a-5664-4183-950a-3a8d9900da84
SCIP notification number (Romania)
672a7a97-23dc-4e7b-9b3a-6261443cdd1a
SCIP notification number (Sweden)
da991a9a-9ad1-499b-aab2-d2200958a2cc
Configuration options
Pre-configured
Input signal type
Current
Input signal (A)
0 20 mA
Input resistance (current input)
≤ 50 Ω
Input current (max.)
50 mA
Input voltage (max.)
30 V
Output signal type
Current
Output signal (A)
0 20 mA
Load impedance (current output)
≤ 600 Ω
Limit frequency
100 Hz
Step response (typ.)
3.5 ms
Transmission error (typ.)
≤ 0.1 % of upper-range value
Temperature coefficient
≤ 0.01 %/K
Power supply type
24 VDC (SELV)
Nominal supply voltage US
DC 24 V
Supply voltage range
±30 %
Current consumption at nominal supply voltage
≤ 30 mA
Current consumption
≤ 40 mA
Test voltage (input/output/supply)
AC 3 kV; 50 Hz; 1 min
Overvoltage category
II
Pollution degree
2
Insulation type (input IN 2.1/relay output)
Functional insulation
Insulation type (adjacent devices)
Reinforced insulation (safe isolation)
JUMPFLEX Signal Conditioner; Isolation Amplifier; 857-411 - WAGO | INDSLT