Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Device-specific
Number of network variables: max. 254 (249 for application)
Transceiver
FTX2
Topology
per LON specification
Number of aliases (max.)
127
Transmission rate
0.078 mbit/s
Bus segment length (max.)
500 m (free topology); 2700 m (bus topology)
Transmission medium
Twisted pair FTT
Transmission channel
1
Data width
24-byte data
Commissioning
via WAGO-I/O-CHECK or WAGO-I/O-PROV2.3
Supply voltage (system)
5 VDC; Via data contacts
Current consumption (5 V system supply)
30mA
Supply voltage (field)
24 VDC; via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Isolation
500 V system/field
Indicators
LED (A, B, C, E, F) green: user configuration, TxD, mailbox, LonWorks status, RxD; LED (G) red: communication/initialization phase; LED (D, H) yellow: service, service
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Connection technology: inputs / outputs
8 x CAGE CLAMP®
Connection type 1
Inputs/Outputs
Solid conductor
0.08 … 2.5 mm2 / 28 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm2 / 28 14 AWG
Strip length
9 10 mm / 0.35 0.39 inches
Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
69 mm / 2.717 inches
Depth from upper-edge of DIN-rail
61.8 mm / 2.433 inches
Mounting type
DIN-35 rail
Pluggable connector
Pluggable
Housing material
Polycarbonate; polyamide 6.6
Fire load
1.046MJ
Weight
54.8g
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-40 … 85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 2000 m / 0 6562 ft
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)
95%
Vibration resistance
per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2
EMC emission of interference
per EN 61000-6-3
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%