2 bits (1 bit current monitoring, 1 bit fuse fault)
Supply voltage (system)
5 VDC; Via data contacts
Current consumption (5 V system supply)
5mA
Supply voltage (field)
24 VDC (-25 +30 %); via power jumper contacts (power supply via CAGE CLAMP®connection; transmission (field-side supply voltage only) via spring contact
Indicators
LED (A) red: defective fuse error; LED (B) green: power supply status
Number of outgoing power jumper contacts
3
Current carrying capacity (power jumper contacts)
6.3A
Connection technology: field supply
6 x CAGE CLAMP®
Connection type 1
Field supply
Solid conductor
0.08 … 2.5 mm2 / 28 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm2 / 28 14 AWG
Strip length
8 9 mm / 0.31 0.35 inches
Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail
62.6 mm / 2.465 inches
Mounting type
DIN-35 rail
Housing material
Polycarbonate; polyamide 6.6
Fire load
1.705MJ
Weight
46.8g
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-40 … 85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 2000 m / 0 6562 ft
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)
95%
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-4, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%