FeatureDurable Construction from Polycarbonate/Polyamide 6.6
9
FeatureCE Marked for Compliance with EU Standards
10
Compact Size3.937 in H x 2.44 in W x 2.831 in D
Number of modules without a bus extension (max.)
64
Input and output process image (fieldbus) max.
1020 words/1020 words
Supply voltage (system)
24 VDC (-25 +30 %); via pluggable connector (CAGE CLAMP®connection)
Current consumption (5 V system supply)
300mA
Total current (system supply)
1,700mA
Supply voltage (field)
24 VDC (-25 +30 %); via power jumper contacts
Input current (typ.) at nominal load (24 V)
480mA
Power supply efficiency (typ.) at nominal load (24 V)
90%
Isolation
500 V system/field
Number of outgoing power jumper contacts
3
Current carrying capacity (power jumper contacts)
10A
Indicators
LED (LINK/ACT) green: Network connection via ports 1 2; LED (MS, NS) red/green: Status of node, network; LED (I/O) red/green/orange: Status of local data bus
Connection technology: communication/fieldbus
EtherNet/IPTM: 2 x RJ-45
Connection technology: field supply
6 x CAGE CLAMP®
Connection technology: system supply
2 x CAGE CLAMP®
Connection type 1
System/field supply
Solid conductor
0.08 2.5 mm2 / 28 14 AWG
Fine-stranded conductor
0.08 2.5 mm2 / 28 14 AWG
Strip length
8 9 mm / 0.31 0.35 inches
Connection technology: device configuration
1 x Male connector; 4-pole
Width
62 mm
Height
100 mm / 3.937 inches
Depth
71.9 mm / 2.831 inches
Depth from upper-edge of DIN-rail
64.7 mm / 2.547 inches
Mounting type
DIN-35 rail
Housing material
Polycarbonate; polyamide 6.6
Fire load
2.461MJ
Weight
147.3g
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 2000 m / 0 6562 ft
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)
95%
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-3, marine applications
Exposure to pollutants
per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%
10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%