{ DescriptionAdvanced Features: Built-in overload relay, ground fault protection, and phase imbalance/failure protection ensure reliable operation in demanding applications. }
2
{ DescriptionSustainable Performance: Designed with energy efficiency in mind, the LC1G400KUEN reduces energy consumption and operates within a wider voltage bandwidth. }
3
{ DescriptionEasy Maintenance: The cable memory kit simplifies maintenance, saving downtime and improving productivity. }
4
{ DescriptionCompliance and Certifications: Compliant with RoHS/REACH regulations and certified for environmental performance, ensuring compliance with the latest standards. }
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
{ DescriptionVersatile Coil Design: The coil is designed for less energy consumption and operates within a wider voltage range, making it versatile for various applications. }
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current
550 A (at <104 °F (40 °C)) at <= 1000 V AC-1400 A (at <140 °F (60 °C)) at <= 440 V AC-3
3.6 kA - 10 s2.4 kA - 30 s1.7 kA - 1 min1.2 kA - 3 min1.0 kA - 10 min
Associated fuse rating
500 A aM at <= 440 V for motor315 A aM at <= 690 V for motor630 A gG at <= 690 V
Average impedance
0.0001 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
30 W AC-1 - Ith 550 A16 W AC-3 - Ith 400 A
compatibility code
LC1G
Pole contact composition
3 NO
Auxiliary contact composition
1 NO + 1 NC
Motor power kW
110 kW at 230 V AC 50/60 Hz (AC-3e)200 kW at 400 V AC 50/60 Hz (AC-3e)200 kW at 415 V AC 50/60 Hz (AC-3e)250 kW at 440 V AC 50/60 Hz (AC-3e)250 kW at 500 V AC 50/60 Hz (AC-3e)315 kW at 690 V AC 50/60 Hz (AC-3e)220 kW at 1000 V AC 50/60 Hz (AC-3e)110 kW at 230 V AC 50/60 Hz (AC-3)200 kW at 400 V AC 50/60 Hz (AC-3)200 kW at 415 V AC 50/60 Hz (AC-3)250 kW at 440 V AC 50/60 Hz (AC-3)250 kW at 500 V AC 50/60 Hz (AC-3)315 kW at 690 V AC 50/60 Hz (AC-3)220 kW at 1000 V AC 50/60 Hz (AC-3)110 kW at 230 V AC 50/60 Hz (AC-4)200 kW at 400 V AC 50/60 Hz (AC-4)200 kW at 415 V AC 50/60 Hz (AC-4)220 kW at 440 V AC 50/60 Hz (AC-4)250 kW at 500 V AC 50/60 Hz (AC-4)315 kW at 690 V AC 50/60 Hz (AC-4)220 kW at 1000 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating
125 hp at 200/208 V 60 Hz150 hp at 230/240 V 60 Hz300 hp at 460/480 V 60 Hz400 hp at 575/600 V 60 Hz
Irms rated making capacity
5090 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Safety reliability level
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
IP2X front face with shrouds IEC 60529IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation
-13...140 °F (-25...60 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Mechanical robustness
Vibrations 5...300 Hz 2 gn contactor openVibrations 5...300 Hz 4 gn contactor closedShocks 10 gn 11 ms contactor openShocks 15 gn 11 ms contactor closed
color
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device