The Harmony XB5 selector switch is a flush-mounted, grey bezel option with a 30mm diameter and 3 positions, designed for simplicity, flexibility, and robustness.
Product ModelXB5FG33C0
Product ID36130
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureSimplicity of installation makes it easy to integrate into any electrical system.
2
FeatureFlexible design allows for various applications in residential and commercial settings.
3
FeatureRobust construction ensures long-lasting performance and reliability.
4
FeatureFlush-mounted design provides a sleek and modern appearance.
5
FeatureIdeal for smart home technologies and energy-efficient solutions.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Harmony XB5
Product or Component Type
Selector switch
Device short name
XB5F
Bezel material
Plastic colour plated grey
Head type
Built-in-flush
Mounting diameter
1.2 in (30.5 mm)
Sale per indivisible quantity
1
Shape of signaling unit head
Round
Type of operator
Stay put stay put
Operator profile
Black key switch, unmarked
Operator position information
3 positions +/- 45°
Type of Keylock
Key 455
Contacts type and composition
2 NO
Contact operation
Slow-break
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1Screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1
Height
1.7 in (42 mm)
Width
1.4 in (36.6 mm)
Depth
3.9 in (98.5 mm)
Terminals description ISO n°1
(13-14)NO(23-24)NO
Resistance to high pressure washer
1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m
Key withdrawal position
Center
Contacts usage
Standard contacts
Positive opening
Without
Mechanical durability
1000000 cycles
Tightening torque
7.08...10.6 lbf.in (0.8...1.2 N.m) IEC 60947-1
Shape of screw head
Cross Philips no 1Cross pozidriv No 1Slotted flat à 4 mmSlotted flat à 5.5 mm
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
10 A cartridge fuse gG IEC 60947-5-1
[Ith] conventional free air thermal current
10 A IEC 60947-5-1
[Ui] rated insulation voltage
600 V 3)IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-1
[Ie] rated operational current
3 A 240 V, AC-15, A600 IEC 60947-5-16 A 120 V, AC-15, A600 IEC 60947-5-10.1 A 600 V, DC-13, Q600 IEC 60947-5-10.27 A 250 V, DC-13, Q600 IEC 60947-5-10.55 A 125 V, DC-13, Q600 IEC 60947-5-11.2 A 600 V, AC-15, A600 IEC 60947-5-1
Electrical durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
Electrical reliability
Î < 10exp(-6) 5 V, 1 mA in clean environment IEC 60947-5-4Î < 10exp(-8) 17 V, 5 mA in clean environment IEC 60947-5-4
Device presentation
Complete product
Protective treatment
TH
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Ambient Air Temperature for Operation
-40...158 °F (-40...70 °C)
Electrical shock protection class
Class II IEC 60536
IP degree of protection
IP66 IEC 60529IP67
NEMA degree of protection
NEMA 13NEMA 4X
IK degree of protection
IK03 conforming to IEC 50102
Standards
IEC 60947-1UL 508JIS C8201-5-1IEC 60947-5-4IEC 60947-5-1CSA C22.2 No 14JIS C8201-1
Product Certifications
UL ListedCSA
Vibration resistance
5 gn 2...500 Hz)IEC 60068-2-6
Shock resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-2750 gn 11 ms) half sine wave acceleration IEC 60068-2-27