Product ModelXB5AK135B5C0
Product ID35797
Stock on Request
Last updated: 8/29/2026
Key Features
1
High EfficiencyThe XB5AK135B5C0 operates at optimal levels, reducing energy consumption and increasing productivity.
2
Reliable PerformanceBuilt with durable components, this device ensures consistent performance in demanding applications.
3
Versatile UseSuitable for a wide range of applications, from residential to industrial settings.
4
Superior QualityEngineered with precision, the XB5AK135B5C0 meets the highest standards of quality and reliability.
5
Easy InstallationDesigned for simplicity, the device is easy to install and maintain, minimizing downtime.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Harmony XB5
Product or Component Type
Illuminated selector switch
Device short name
XB5
Bezel material
Plastic colour plated grey
Head type
Standard
Mounting diameter
0.9 in (22.5 mm)
Sale per indivisible quantity
1
Shape of signaling unit head
Round
Type of operator
stay put
Operator profile
Orange standard handle
Operator position information
3 positions +/- 45°
Contacts type and composition
1 NO + 1 NC
Contact operation
Slow-break
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1Screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1
Bulb base
Integral LED
[Us] rated supply voltage
24 V AC/DC 50/60 Hz
Height
1.7 in (42 mm)
Width
1.2 in (30 mm)
Depth
2.8 in (70 mm)
Terminals description ISO n°1
(13-14)NO(11-12)NC
Net Weight
1.138 lb(US) (0.516 kg)
Resistance to high pressure washer
1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m
Contacts usage
Standard contacts
Positive opening
With IEC 60947-5-1 appendix K
Operating torque
1.24 lbf.in (0.14 N.m) NO changing electrical state
Mechanical durability
500000 cycles
Tightening torque
7.08...10.6 lbf.in (0.8...1.2 N.m) IEC 60947-1
Shape of screw head
Cross Philips no 1Cross pozidriv No 1Slotted flat à 4 mmSlotted flat à 5.5 mm
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
10 A cartridge fuse gG IEC 60947-5-1
[Ith] conventional free air thermal current
10 A IEC 60947-5-1
[Ui] rated insulation voltage
600 V 3)IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-1
[Ie] rated operational current
3 A 240 V, AC-15, A600 IEC 60947-5-16 A 120 V, AC-15, A600 IEC 60947-5-10.1 A 600 V, DC-13, Q600 IEC 60947-5-10.27 A 250 V, DC-13, Q600 IEC 60947-5-10.55 A 125 V, DC-13, Q600 IEC 60947-5-11.2 A 600 V, AC-15, A600 IEC 60947-5-1
Electrical durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
Electrical reliability
Î < 10exp(-6) 5 V 1 mA in clean environment IEC 60947-5-4Î < 10exp(-8) 17 V 5 mA in clean environment IEC 60947-5-4
Signalling type
Steady
Light source
Universal LED
Supply voltage limits
19.2...30 V DC21.6...26.4 V AC
current consumption
18 mA
Service life
100000 h at rated voltage and 25 °C
Surge withstand
1 kV IEC 61000-4-5
Device presentation
Complete product
Protective treatment
TH
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Ambient Air Temperature for Operation
-40...158 °F (-40...70 °C)
Electrical shock protection class
Class II IEC 60536
IP degree of protection
IP66 IEC 60529IP67 IEC 60529
NEMA degree of protection
NEMA 13NEMA 4X
IK degree of protection
IK05 conforming to IEC 50102
Standards
UL 508IEC 60947-1JIS C8201-5-1IEC 60947-5-4CSA C22.2 No 14IEC 60947-5-1JIS C8201-1
Product Certifications
CSABVLROS (Lloyds register of shipping)DNVUL
Vibration resistance
5 gn 2...500 Hz)IEC 60068-2-6
Shock resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-2750 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Resistance to fast transients
2 kV IEC 61000-4-4
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3
Resistance to electrostatic discharge
6 kV on contact (on metal parts) IEC 61000-4-28 kV in free air (in insulating parts) IEC 61000-4-2