High ReliabilitySolid state protection for reliable operation.
2
Technical Specifications64 outputs, 24 V DC positive voltage, and overvoltage protection by transil diode.
3
CompatibilityDesigned for Modicon Premium Automation platforms.
4
Efficient DesignMinimal power dissipation for reduced heat and increased performance.
5
ComplianceMeets international standards including UL 508, CSA C22.2 No 213 Class I Division 2 Group A, and IEC 61131-2.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Modicon Premium Automation platform
Product or Component Type
Discrete output module
Discrete output number
64
Discrete output type
Solid state protected
Discrete output voltage
24 V DC positive EN/IEC 61131-2 19...30 V
Current per channel
0.1 A
Maximum current per module
5 A
Maximum leakage current
0.1 mA 30 V
Maximum tungsten load
1.2 W
[Ures] residual voltage
1.5 V
Response time
1.2 ms
Paralleling of outputs
Yes : 3 maximum
Output overvoltage protection
By transil diode
Reverse polarity protection
Reverse mounted diode
Output overload protection
Automatic trip
Short-circuit protection
Automatic trip
Minimum load impedance
220 W at state 1
isalotion resistance
> 10 MOhm 500 V
Power dissipation
(2.4 W + 0.1 W x No of outputs)
Product Compatibility
Dial and Power
marking
CE
Electrical connection
4 connectors HE-10
Current consumption
155 mA 5 V DC
Module format
Standard
Net Weight
0.79 lb(US) (0.36 kg)
Dielectric strength
1500 V 50/60 Hz 60 s
Standards
UL 508CSA C22.2 No 213 Class I Division 2 Group ACSA C22.2 No 213 Class I Division 2 Group C93/68/EEC89/336/EECIEC 61131-2CSA C22.2 No 142CSA C22.2 No 213 Class I Division 2 Group B92/31/EECCSA C22.2 No 213 Class I Division 2 Group D73/23/EEC
Product Certifications
RINADNVBVABSGLRMRSLR
Ambient Air Temperature for Operation
32...140 °F (0...60 °C)
Ambient Air Temperature for Storage
-13...158 °F (-25...70 °C)
Relative Humidity
10...95 % without condensation for operation5...95 % without condensation for storage