2 A 250 V AC inductive - cos phi = 0.4 - L/R = 7 ms R1-R2)2 A 30 V DC inductive - cos phi = 0.4 - L/R = 7 ms R1-R2)5 A 250 V AC resistive - cos phi = 1 - L/R = 0 ms R1-R2)5 A 30 V DC resistive - cos phi = 1 - L/R = 0 ms R1-R2)
Discrete input number
6
Discrete input type
LI1...LI6) programmable 24 V, 0...100 mA PLC 3500 Ohm
Acceleration and deceleration ramps
S, U or customizedLinear adjustable separately from 0.1 to 999.9 s
Braking to standstill
By DC injection
Protection type
Input phase breaks driveLine supply overvoltage and undervoltage safety circuits driveLine supply phase loss safety function, for three phases supply driveMotor phase breaks driveOvercurrent between output phases and earth (on power up only) driveOverheating protection driveShort-circuit between motor phases driveThermal protection motor
Insulation resistance
>= 500 mOhm 500 V DC for 1 minute
Local signalling
for drive voltage 1 LED (red) for CANopen bus status four 7-segment display units
Time constant
5 ms for reference change
Frequency resolution
Display unit 0.1 HzAnalog input 0.1...100 Hz
communication port protocol
ModbusCANopen
Connector type
1 RJ45 CANopen via VW3 CANTAP2 adaptor1 RJ45 Modbus
Physical interface
RS485 multidrop serial link Modbus
Transmission frame
RTU Modbus
Transmission Rate
10, 20, 50, 125, 250, 500 kbps or 1 Mbps CANopen via VW3 CANTAP2 adaptor4800, 9600 or 19200 bps Modbus
Number of addresses
1...127 CANopen via VW3 CANTAP2 adaptor1...247 Modbus
Number of drive
127 CANopen via VW3 CANTAP2 adaptor31 Modbus
marking
CE
Operating position
Vertical +/- 10 degree
Net Weight
23.6 lb(US) (10.7 kg)
Dielectric strength
2410 V DC between earth and power terminals3400 V AC between control and power terminals
Electromagnetic compatibility
1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5Electrical fast transient/burst immunity test level 4 IEC 61000-4-4Electrostatic discharge immunity test level 3 IEC 61000-4-2Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
Standards
EN 50178
Product Certifications
ULC-tickN998CSA
Pollution degree
2
Protective treatment
TC
Vibration resistance
1 gn 13...150 Hz)EN/IEC 60068-2-61.5 mm 3...13 Hz)EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Relative humidity
5...95 % without condensation IEC 60068-2-35...95 % without dripping water IEC 60068-2-3
Ambient Air Temperature for Storage
-13...158 °F (-25...70 °C)
Ambient air temperature for operation
14...122 °F (-10...50 °C) without derating with protective cover on top of the drive)14...140 °F (-10...60 °C) with derating factor without protective cover on top of the drive)
Operating altitude
<= 3280.84 ft (1000 m) without derating>= 3280.84 ft (1000 m) with current derating 1 % per 100 m