Analogue input type
NTC NK103 Beta 3977 temperature probe - 40...137 °C 0.1 °C 10 kOhm at 25 °C)NTC 103AT-2 Beta 3435 temperature probe - 50...110 °C 0.1 °C 10 kOhm at 25 °C) voltage 0...10 V 1 digit > 10 kOhm voltage 0...5 V 1 digit > 20 kOhm absolute or ratiometric) impedance 0...1500 hOhm 1 hOhm 10 kOhm impedance 0...300 daOhm 1 daOhm 1500 OhmPTC temperature probe - 55...150 °C 0.1 °C 1500 OhmPt 1000 temperature probe - 200...850 °C 0.1 °C 1500 Ohm current 0...20 mA/4...20 mA 1 digit < 150 Ohm direct input 10 kOhm Dry contact)
Measurement accuracy
0...20 mA 0...4 mA +/- 2 % of full scale +/- 1 digit0...20 mA 4...20 mA +/- 1 % of full scale +/- 1 digit4...20 mA +/- 1 % of full scale +/- 1 digit0...10 V +/- 1 % of full scale +/- 1 digit0...5 V +/- 1 % of full scale +/- 1 digitDaOhm 0...300 daOhm +/- 2.5 daOhm NTC NK103 Beta 3977 - 40...+110 °C +/- 1 °C NTC NK103 Beta 3977 110...137 °C +/- 1.9 °C NTC 103AT-2 Beta 3435 - 50...110 °C +/- 1 °C PTC - 55...155 °C +/- 1.1 °C Pt 1000 - 200...-100 °C +/- 10 °C Pt 1000 - 100...-50 °C +/- 2.5 °C Pt 1000 - 50...100 °C +/- 1.5 °C Pt 1000 100...400 °C +/- 2.4 °C Pt 1000 400...850 °C +/- 10 °CHOhm 0...750 hOhm +/- 8.5 hOhmHOhm 750 hOhm...1500 hOhm +/- 24 hOhm