Analogue input type
NTC NK103 Beta 3977 temperature probe - 40...137 °C 0.1 °C 10 kOhm at 25 °C)NTC 103AT-2 Beta 3435 temperature probe - 50...110 °C 0.1 °C 10 kOhm at 25 °C) current 0...20 mA 1 digit < 150 Ohm current 4...20 mA 1 digit < 150 Ohm voltage 0...10 V 1 digit > 10 kOhm voltage 0...5 V 1 digit > 20 kOhm absolute or ratiometric) impedance 0...1500 hOhm 1 hOhm 10 kOhm impedance 0...300 daOhm 1 daOhm 2 kOhmPt 100/Pt 1000 PTC - 55...150 °C 0.1 °C 2 kOhm direct input 1 digit Dry contact) Pt 1000 temperature probe - 200...850 °C 0.1 °C 2 kOhm
Measurement accuracy
NTC NK103 - 40...+110 °C +/- 1 °C NTC NK103 110...137 °C +/- 1.9 °C NTC 103AT-2 - 50...110 °C +/- 1 °C PTC - 55...+135 °C +/- 1.1 °C PTC - 150...135 °C +/- 3.1 °C Pt 1000 - 200...-100 °C +/- 5 °C Pt 1000 - 100...-50 °C +/- 3 °C Pt 1000 - 50...+200 °C +/- 1.5 °C Pt 1000 200...600 °C +/- 15 °C Pt 1000 600...850 °C +/- 30 °C0...20 mA 0...4 mA +/- 2 % of full scale +/- 1 digit0...20 mA 4...20 mA +/- 1 % of full scale +/- 1 digit4...20 mA +/- 1 % of full scale +/- 1 digit0...10 V +/- 1 % of full scale +/- 1 digit0...5 V +/- 1 % of full scale +/- 1 digitHOhm 0...700 hOhm +/- 10 hOhmHOhm 700 hOhm...1200 hOhm +/- 25 hOhmHOhm 1200 hOhm...1500 hOhm +/- 60 hOhmDaOhm 0...300 daOhm +/- 2.5 daOhm