+/- 10 % of the full scale value+/- 20 % for the HS range
Repeat accuracy
+/- 2 % time delay
Measurement error
0.5 %/°C with temperature variation
Sensitivity adjustment
5...100 %
Maximum supply current for sensors
40 mA
Cable capacitance
10 nF probe cable
marking
CE : EMC 89/336/EECCE : 73/23/EEC
Overvoltage category
III IEC 60664-1
Insulation resistance
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5> 500 MOhm 500 V DC between measurement and relay output IEC 60664-1> 1 MOhm 500 V DC between supply and measurement IEC 60255-5> 500 MOhm 500 V DC between supply and relay output IEC 60664-1> 500 MOhm 500 V DC between measurement and relay output IEC 60255-5> 1 MOhm 500 V DC between supply and measurement IEC 60664-1
[Ui] rated insulation voltage
250 V IEC 60664-1
Operating position
Any position without derating
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable endScrew terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable endScrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
Tightening torque
5.3...8.9 lbf.in (0.6...1 N.m) IEC 60947-1
Housing material
Self-extinguishing plastic
Local signalling
for relay ON LED (yellow) for power ON LED (green) for timer ON LED (yellow)
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour full load
Safety reliability data
B10d = 170000MTTFd = 182.6 years
Width
1.4 in (35 mm)
Control Type
Without test button
Immunity to microbreaks
100 ms DC90 ms AC
Electromagnetic compatibility
Emission standard for industrial environments conforming to IEC 61000-6-4Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards
IEC 60255-6
Product Certifications
GOSTCSAULGLC-tick
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Ambient air temperature for operation
-4...122 °F (-20...50 °C)
Relative humidity
95 % 131 °F (55 °C) IEC 60068-2-30
IP degree of protection
IP20 IEC 60529 terminals)IP30 IEC 60529 casing)
Pollution degree
3 IEC 60664-1
Dielectric test voltage
2 kV AC 50 Hz, 1 min IEC 60255-52 kV AC 50 Hz, 1 min IEC 60664-1
RM35LV14MW - Liquid Level Control Relay | Harmony Control Relays | INDSLT