<= 3.5 s + Tt (in case of temperature fault)500 ms (in case of 3-phase fault)500 ms (on disappearance of fault)
Temperature probe type
Pt 100 - 3-wire
Installed device
Pt 100 probe cable length <= 10 m
marking
CE : EMC 89/336/EECCE : 73/23/EEC
Overvoltage category
III IEC 60664-1
Insulation resistance
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5> 500 MOhm 500 V DC between measurement and relay output IEC 60664-1> 1 MOhm 500 V DC between supply and measurement IEC 60255-5> 500 MOhm 500 V DC between supply and relay output IEC 60664-1> 500 MOhm 500 V DC between measurement and relay output IEC 60255-5> 1 MOhm 500 V DC between supply and measurement IEC 60664-1
[Ui] rated insulation voltage
400 V IEC 60664-1
operating voltage tolerance
- 10 % + 10 % Un DC- 15 % + 10 % Un AC
Supply frequency
50/60 Hz +/- 10 %
Operating position
Any position without derating
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable endScrew terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable endScrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Tightening torque
5.3...8.9 lbf.in (0.6...1 N.m) IEC 60947-1
Housing material
Self-extinguishing plastic
local signalling
1 LED Green power ON1 LED Yellow correct temperature (high R1)/(low R2)1 LED Yellow phases of relay
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour full load
Control Type
Without test button
Immunity to microbreaks
10 ms
Electromagnetic compatibility
Emission standard for industrial environments IEC 61000-6-4Emission standard for residential, commercial and light-industrial environments IEC 61000-6-3Immunity for industrial environments NF EN/IEC 61000-6-2
Standards
NF EN 60255-6IEC 60255-6
Product Certifications
GLULC-tickCSAGOST
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Ambient Air Temperature for Operation
-4...122 °F (-20...50 °C)
Vibration resistance
0.35 mm 5...57.6 Hz)IEC 60068-2-6/IEC 60255-21-11 gn 57.6...150 Hz)IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn 11 ms IEC 60255-21-1
IP degree of protection
IP20 IEC 60529 terminals)IP30 IEC 60529 casing)
Pollution degree
3 IEC 60664-1
Dielectric test voltage
2 kV AC 50 Hz, 1 min
Non-dissipating shock wave
4 kV