<= 3.5 s + Tt (in case of temperature fault)<= 3.5 s (on disappearance of fault)
Temperature probe type
Pt 100 - 3-wire
Installed device
Pt 100 probe cable length <= 10 m
marking
CE : EMC 89/336/EECCE : 73/23/EEC
Overvoltage category
III IEC 60664-1
Insulation resistance
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5> 500 MOhm 500 V DC between measurement and relay output IEC 60664-1> 1 MOhm 500 V DC between supply and measurement IEC 60255-5> 500 MOhm 500 V DC between supply and relay output IEC 60664-1> 500 MOhm 500 V DC between measurement and relay output IEC 60255-5> 1 MOhm 500 V DC between supply and measurement IEC 60664-1
[Ui] rated insulation voltage
250 V IEC 60664-1
operating voltage tolerance
- 10 % + 10 % Un DC- 15 % + 10 % Un AC
Supply frequency
50/60 Hz +/- 10 %
Insulation
Galvanic insulation between supply and measurement
Operating position
Any position without derating
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable endScrew terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable endScrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Tightening torque
5.3...8.9 lbf.in (0.6...1 N.m) IEC 60947-1
Housing material
Self-extinguishing plastic
local signalling
1 LED Green power ON1 LED Yellow correct temperature (high R1)1 LED Yellow correct temperature (low R2)
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour full load
Control Type
Without test button
Immunity to microbreaks
10 ms
Electromagnetic compatibility
Emission standard for industrial environments IEC 61000-6-4Emission standard for residential, commercial and light-industrial environments IEC 61000-6-3Immunity for industrial environments NF EN/IEC 61000-6-2
Standards
IEC 60255-6NF EN 60255-6
Product Certifications
GLGOSTC-tickCSAUL
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Ambient Air Temperature for Operation
-4...122 °F (-20...50 °C)
Vibration resistance
0.35 mm 5...57.6 Hz)IEC 60068-2-6/IEC 60255-21-11 gn 57.6...150 Hz)IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn 11 ms IEC 60255-21-1
IP degree of protection
IP20 IEC 60529 terminals)IP30 IEC 60529 casing)
Pollution degree
3 IEC 60664-1
Dielectric test voltage
2 kV AC 50 Hz, 1 min
Non-dissipating shock wave
4 kV
Temperature Control Relay RM35ATR5MW by Schneider Electric | INDSLT