<= 0.05 % per degree centigrade depending permissible ambient air temperature<= 1 % within the supply voltage range
Setting accuracy of time delay
10 P
Time delay drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature<= 1 % within the supply voltage range
Hysteresis
2 % fixed selectable
Run-up delay at power-up
650 ms
Maximum measuring cycle
150 ms measurement cycle as true rms value
Threshold adjustment voltage
2...20 % of Un selected
Voltage range
200...240 V phase to phase
Repeat accuracy
+/- 0.5 % input and measurement circuit
Measurement error
< 1 % over the whole range with voltage variation< 0.05 %/°C with temperature variation
Response time
<= 300 ms
Overvoltage category
III IEC 60664-1III UL 508
Insulation resistance
> 100 MOhm 500 V DC IEC 60255-27
Mounting position
Any position
Connections - terminals
Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable endScrew terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable endScrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1Immunity for industrial environments conforming to IEC 61000-6-2Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3Emission standard for industrial environments conforming to IEC 61000-6-4Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5Conducted and radiated emissions class B group 1 conforming to CISPR 11Conducted and radiated emissions class B conforming to CISPR 22
0.075 mm 10...58.1 Hz) not in operation IEC 60068-2-61 gn 10...58.1 Hz) not in operation IEC 60068-2-60.035 mm 58.1...150 Hz) in operation IEC 60068-2-60.5 gn 58.1...150 Hz) in operation IEC 60068-2-6
Shock resistance
15 gn 11 ms) not in operation IEC 60068-2-275 gn 11 ms) in operation IEC 60068-2-27