1
High Power Rating400 kW at 440 V AC 50/60 Hz (AC-3)
2
Durable DesignBuilt to withstand demanding industrial conditions
3
Easy InstallationSimple and efficient installation process
4
Versatile UseSuitable for a wide range of industrial applications
5
Reliable PerformanceEnsures consistent and reliable operation
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive loadMotor control
Utilisation category
AC-3AC-4AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<= 460 V DC
[Uc] control circuit voltage
415 V AC 40...400 Hz
[Ie] rated operational current
1000 A (at <104 °F (40 °C)) at <= 440 V AC AC-1630 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
1000 A (at 104 °F (40 °C))1250 A
Rated breaking capacity
5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
5050 A 104 °F (40 °C) - 10 s4400 A 104 °F (40 °C) - 30 s3400 A 104 °F (40 °C) - 1 min2200 A 104 °F (40 °C) - 3 min1600 A 104 °F (40 °C) - 10 min
Associated fuse rating
1000 A gG at <= 440 V630 A aM at <= 440 V
Average impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
120 W AC-148 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
335 kW at 380...400 V AC 50/60 Hz (AC-3)375 kW at 415 V AC 50/60 Hz (AC-3)400 kW at 440 V AC 50/60 Hz (AC-3)400 kW at 500 V AC 50/60 Hz (AC-3)450 kW at 660...690 V AC 50/60 Hz (AC-3)450 kW at 1000 V AC 50/60 Hz (AC-3)200 kW at 220...230 V AC 50/60 Hz (AC-3)100 kW at 400 V AC 50/60 Hz (AC-4)