Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current
1000 A 104 °F (40 °C)) <= 440 V AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
1000 A (at 104 °F (40 °C))1250 A
Irms rated making capacity
6300 A AC conforming to IEC 60947-4-1
Rated breaking capacity
5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
5050 A 104 °F (40 °C) - 10 s4400 A 104 °F (40 °C) - 30 s3400 A 104 °F (40 °C) - 1 min2200 A 104 °F (40 °C) - 3 min1600 A 104 °F (40 °C) - 10 min
Associated fuse rating
630 A aM at <= 440 V1000 A gG at <= 440 V
Average impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
120 W AC-148 W AC-3
Mounting Support
Plate
Standards
EN 60947-4-1JIS C8201-4-1IEC 60947-4-1EN 60947-1IEC 60947-1
Product Certifications
RMRoSRINADNVCBABSCSALROS (Lloyds register of shipping)ULBV
Connections - terminals
Power circuit bar 2 60 x 5 mm
Tightening torque
Power circuit 513.3 lbf.in (58 N.m)
Mechanical durability
5 Mcycles
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23...131 °F (-5...55 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
-40...158 °F (-40...70 °C) at Uc
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzVibrations contactor closed4 Gn, 5...300 HzShocks contactor open6 Gn for 1/2 sine wave (11 ms)Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)