The LC1F6302 is a high-performance contactor and starter designed for motor control applications, offering reliability and efficiency.
Product ModelLC1F6302
Product ID33499
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance motor control for reliable operation.
2
FeatureEfficient design for reduced energy consumption.
3
FeatureDurable construction with resistant materials.
4
FeatureCompliant with IEC standards for global compatibility.
5
FeatureEasy installation and maintenance for reduced downtime.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
2P
power pole contact composition
2 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current
1250 A 104 °F (40 °C)) <= 440 V AC AC-11000 A 104 °F (40 °C)) <= 440 V AC AC-1
[Uc] control circuit voltage
48...1000 V AC 40...400 Hz with LX1/LX9 coil48...440 V DC with LX4 coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
1000 A (at 104 °F (40 °C))1250 A
Irms rated making capacity
6300 A AC conforming to IEC 60947-4-1
Rated breaking capacity
5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
5050 A 104 °F (40 °C) - 10 s4400 A 104 °F (40 °C) - 30 s3400 A 104 °F (40 °C) - 1 min2200 A 104 °F (40 °C) - 3 min1600 A 104 °F (40 °C) - 10 min
Associated fuse rating
630 A aM at <= 440 V1000 A gG at <= 440 V
Average impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
120 W AC-1
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coilDrop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coilOperational: 0.85...1.1 Uc DC with LX4 coilDrop-out: 0.2...0.35 Uc DC with LX4 coil
Heat dissipation
20 W
Operating time
40...80 ms closing with LX1/LX9 coil100...200 ms opening with LX1/LX9 coil60...70 ms closing with LX4 coil40...50 ms opening with LX4 coil
Mounting Support
Plate
Standards
EN 60947-4-1IEC 60947-4-1IEC 60947-1JIS C8201-4-1EN 60947-1
Product Certifications
ABSULRINADNVCSACBLROS (Lloyds register of shipping)BVRMRoSUKCA
1500...1730 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil1420...1920 VA (at 68 °F (20 °C))with LX4 coil
Hold-in power consumption in VA
20...25 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil6.5...12.5 VA (at 68 °F (20 °C))with LX4 coil
Maximum operating rate
1200 cyc/h 131 °F (55 °C)
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23...131 °F (-5...55 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
-40...158 °F (-40...70 °C)
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzVibrations contactor closed4 Gn, 5...300 HzShocks contactor open6 Gn for 1/2 sine wave (11 ms)Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
12.0 in (304 mm)
Width
12.2 in (309 mm)
Depth
10.04 in (255 mm)
Net Weight
34.2 lb(US) (15.5 kg)
LC1F6302 - Schneider Electric Contactors and Starters | INDPRT