High-power magnetic contactor for motor applications up to 250kW at 400V.
Product ModelLC1F500X722L
Product ID33496
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh durability with 2400 cycles/hour operating rate.
2
FeatureHigh reliability in environments up to 55°C.
3
FeatureSuitable for motor applications up to 250kW at 400V.
4
FeatureNo coil required for later selection and installation.
5
FeatureComplemented by Class10/20 LR9F type electronic thermal over-load relays and TeSys GV7-R circuit breaker.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor controlResistive load
Utilisation category
AC-4AC-3AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
550...600 V AC 40...400 Hz
[Ie] rated operational current
700 A (at <104 °F (40 °C)) at <= 440 V AC AC-1500 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
700 A (at 104 °F (40 °C))
Rated breaking capacity
4000 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
4200 A 104 °F (40 °C) - 10 s3200 A 104 °F (40 °C) - 30 s2400 A 104 °F (40 °C) - 1 min1500 A 104 °F (40 °C) - 3 min1200 A 104 °F (40 °C) - 10 min
Associated fuse rating
500 A aM at <= 440 V800 A gG at <= 440 V
Average impedance
0.18 mOhm - Ith 700 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
88 W AC-145 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
250 kW at 380...400 V AC 50/60 Hz (AC-3)280 kW at 415 V AC 50/60 Hz (AC-3)295 kW at 440 V AC 50/60 Hz (AC-3)355 kW at 500 V AC 50/60 Hz (AC-3)335 kW at 660...690 V AC 50/60 Hz (AC-3)335 kW at 1000 V AC 50/60 Hz (AC-3)147 kW at 220...230 V AC 50/60 Hz (AC-3)80 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
150 hp at 200 V AC200 hp at 230 V AC400 hp at 460 V AC500 hp at 575 V AC